NEW QUESTION # 10
When designing a hospital, which of the following is the energy standard that should be reviewed?

  • A. ASHRAE 90.2
  • B. ASHRAE 62.1
  • C. ASHRAE 62.2
  • D. ASHRAE 90.1

Answer: D


NEW QUESTION # 11
Which of the following is the MOST important factor when evaluating how effective a Variable Air Volume system will be in saving energy in an area or room?

  • A. Amount of time that the airflow can be reduced
  • B. Number of procedures performed
  • C. Type of procedure being performed
  • D. Size of the area or room

Answer: A


NEW QUESTION # 12
An Operating Room ventilation system must monitor and automatically:

  • A. Alarm when waste anesthetic gas levels are elevated
  • B. Set back the ventilation system when the surgical suite is not in use
  • C. Prevent recirculation of smoke within the surgical suite
  • D. Control the dew point within the room

Answer: A


NEW QUESTION # 13
In accordance with ASHRAE Standard 170, the filter bed #2 in an air-handling unit serving a patient area shall be located:

  • A. After the fan and the cooling coil
  • B. Between the fan and the outside air louver
  • C. After the pre-heat coil and before the fan
  • D. Before the fan and the cooling coil

Answer: A

Explanation:
Comprehensive and Detailed Explanation:
Filter Placement: ASHRAE 170, Section 6.4, requires Filter Bed #1 (MERV 7) before coils and Filter Bed #2 (MERV 14) after the fan and cooling coil to protect patient areas from downstream contaminants.


NEW QUESTION # 14
HVAC design for cardiac catheterization suites must take into account that the facilities:

  • A. Contain significant electrical equipment loads
  • B. Are required to have treatment rooms with negative pressure
  • C. Require infrequent mechanical upgrades
  • D. Are associated with relatively noninvasive procedures

Answer: A


NEW QUESTION # 15
An engineer is designing the Autopsy facilities, the Dietary Department's facilities, the Emergency Department waiting area, and the Waste and Trash areas in a hospital. Which of the following statements accurately describes a consideration that the engineer must take into account when designing these spaces?

  • A. Because the Emergency Department waiting area is not utilized as a patient treatment space, special HVAC consideration of this area is usually not necessary
  • B. Because some of the waste generated by a healthcare facility is hazardous, the Waste and Trash areas must use 100% outside air
  • C. Because cooking surfaces used in the kitchen produce odors typically lighter than air, these rooms do not use local exhaust
  • D. Because Autopsy facilities have the same total ACH and exhaust requirements as Airborne Infection Isolation Rooms, they require special design features

Answer: D


NEW QUESTION # 16
Which of the following is unique to the commissioning of hospital and laboratory ventilation systems?

  • A. System interoperability
  • B. Verification of maximum energy efficiency
  • C. The role of hospitals and laboratories in community disasters
  • D. Room air pressure requirements

Answer: D


NEW QUESTION # 17
In accordance with ASHRAE Standard 170, general hospital Operating Rooms must have a minimum of two return grilles, one of which must be located:

  • A. High, and the other low
  • B. Adjacent to the anesthetizing location
  • C. At breathing height
  • D. As far away from the other as practical

Answer: A

Explanation:
Comprehensive and Detailed Explanation:
OR Ventilation: ASHRAE Standard 170, Section 7.4.1, mandates at least two return/exhaust grilles in ORs, with one high and one low. The low grille (near the floor) removes heavier contaminants, while the high grille aids in overall air circulation, supporting laminar flow from ceiling diffusers.
Option Analysis:
A/B: Breathing height or anesthetizing location are not specified in ASHRAE 170.
C: Distance is practical but not the primary requirement.
D: Correct-high and low placement is explicitly required.


NEW QUESTION # 18
Which of the following is recognized equipment for the commissioning of areas that require unique pressure relationships?

  • A. A handheld micromanometer
  • B. A room air leakage test
  • C. A supply and exhaust measuring station
  • D. A vane anemometer

Answer: A


NEW QUESTION # 19
In accordance with ASHRAE Standard 170, which of the following areas is required to have a positive pressure relationship?

  • A. Nuclear medicine laboratory
  • B. Morgue and autopsy area
  • C. Physical therapy room
  • D. Cystoscopy surgical suite

Answer: D

Explanation:
Comprehensive and Detailed Explanation:
Pressure Requirements: ASHRAE 170, Table 7.1, mandates positive pressure for cystoscopy surgical suites (0.01 in. w.g.) to maintain sterility. Morgue/autopsy (C) and some nuclear medicine areas (D) require negative pressure; physical therapy (B) is typically neutral.


NEW QUESTION # 20
What is the recommended face velocity of Group E diffusers in operating rooms?

  • A. 25 to 35 fpm (0.13 to 0.18 m/s)
  • B. 50 to 60 fpm (0.25 to 0.31 m/s)
  • C. 100 to 110 fpm (0.51 to 0.56 m/s)
  • D. 5 to 15 fpm (0.03 to 0.08 m/s)

Answer: A

Explanation:
Comprehensive and Detailed Explanation:
Group E Diffusers: ASHRAE 170 and the HVAC Design Manual recommend 25-35 fpm for laminar flow diffusers in ORs to maintain low turbulence and effective contaminant removal over the surgical field.


NEW QUESTION # 21
Which of the following areas require HEPA-filtered supply air?

  • A. Emergency Department Waiting Rooms
  • B. Regular Patient Rooms
  • C. Protective Environment Rooms
  • D. Class A Operating Rooms

Answer: C

Explanation:
Comprehensive and Detailed Explanation:
HEPA Requirement: ASHRAE 170, Section 7.2.2, mandates HEPA-filtered supply air (MERV 17) for Protective Environment Rooms to protect immunocompromised patients. Regular patient rooms (6 ACH), ED waiting rooms (negative pressure), and Class A ORs (15 ACH, MERV 14) do not require HEPA.


NEW QUESTION # 22
Compliance with the ASHRAE Standard 90.1 mandatory provisions for Heating, Ventilating, and Air Conditioning can be achieved using the energy cost budget method or:

  • A. Energy modeling
  • B. The building trade-off option
  • C. Simplified approach
  • D. The prescriptive method

Answer: D


NEW QUESTION # 23
A central cooling system is designed so that the number and arrangement of cooling sources is sufficient to support the facility operation plan in case of a breakdown of any one of the cooling sources. According to ASHRAE Standard 170, this applies when the cooling load exceeds a MINIMUM of:

  • A. 4000 tons (14,000 kW)
  • B. 400 tons (1,400 kW)
  • C. 4 tons (14 kW)
  • D. 40 tons (140 kW)

Answer: B


NEW QUESTION # 24
According to the most current edition of ASHRAE Standard 170, which of the following is the correct number of air changes per hour for a treatment room?

  • A. 0
  • B. 1
  • C. 2
  • D. 3

Answer: B


NEW QUESTION # 25
If a hospital is in an area with a very cold climate, which of the following equipment in the central utility plant needs to be redundant with emergency back-up?

  • A. Chillers and associated pumps
  • B. Snow melt systems
  • C. Hot water boilers and associated pumps
  • D. Co-generation units

Answer: C

Explanation:
Comprehensive and Detailed Explanation:
Cold Climate Priority: Hot water boilers and pumps are critical for heating in very cold climates, requiring redundancy and backup per ASHRAE Handbook-HVAC Applications for patient safety.


NEW QUESTION # 26
The Environment of Care™ standards of The Joint Commission establish requirements for which of the following functions?

  • A. Designer qualifications for professionals working in a healthcare organization
  • B. A series of specifications for designing and constructing healthcare facilities
  • C. A set of management standards for application by the healthcare organization
  • D. Absolute minimum requirements for air change rates in rooms and spaces

Answer: C


NEW QUESTION # 27
A Protective Isolation Room, Surgical Cystoscopic Room, or Bronchoscopy Room shall maintain a MINIMUM room differential pressure of:

  • A. 0.01 inch water gauge (2.5 pascals)
  • B. 0.05 inch water gauge (12.5 pascals)
  • C. 0.025 inch water gauge (7.5 pascals)
  • D. 0.10 inch water gauge (25 pascals)

Answer: A


NEW QUESTION # 28
Which of the following is the BEST location for a room thermostat in a typical patient room?

  • A. Near the window
  • B. Below the return air register
  • C. Near the ceiling
  • D. Below the supply air register

Answer: B


NEW QUESTION # 29
Which of the following is the recommended location for Group E (non-aspirating) air diffusers in Operating Rooms?

  • A. In the substerile ceiling
  • B. In the center of the ceiling over the surgical table
  • C. High on the sidewall on at least two opposite walls
  • D. On the perimeter of the room outside of the lights

Answer: B

Explanation:
Comprehensive and Detailed Explanation:
Group E Diffusers: These non-aspirating diffusers provide laminar, downward airflow. ASHRAE Standard
170 and FGI Guidelines recommend placement in the ceiling center, directly above the surgical table, to ensure clean air blankets the sterile field.
Option Analysis:
A: Correct-center ceiling placement is standard for ORs.
B/C: Sidewall or perimeter placement disrupts laminar flow.
D: Substerile areas are adjacent, not the OR itself.


NEW QUESTION # 30
......